CK10W-33/93.5


Notes

  • Typical response time is 25 nS maximum L-N and 100nS maximum N-PE.
  • Meets IEC600 99-4.

Specification

DESCRIPTION specification conditions VALUE
VRMS28050 VAC
Maximum Discharge CurrentIMAXFor 8 x 20 μs Pulse10000 A
Rated Voltage (L-N)VR (L33 kV
Maximum DC Reference VoltageVDCREFAt 1 mA47.3 kV
Maximum Residual VoltageVRESAt Steep of 1 x 10 µs Pulse112.2 kV
Maximum Residual VoltageVRESFor Lightning Impulse 8 x 20 µs96.8 kV
Maximum Residual VoltageVRESFor Switching Impulse 30 x 60 µs82.5 kV
Withstand CapabilityISWCFor Current Impulse 4 x 10 µs100 kA
Housing Insulation LevelVBILFor Lighning Impulse126.5 kV
Housing Insulation LevelVBILAt Power Frequency, Wet 1 Minute88 kV
Mechanical Strength TorsionalStr. Tor50 N m
Mechanical Strength CantileverStr. Can.147 N m
Creepage1127 mm
A1.18
B1.18
C15.51
D17.87 in
E2.32 in
F4.64 in