CK5W-24/68


Notes

  • Typical response time is 25 nS maximum L-N and 100nS maximum N-PE.
  • Made From a Durable Polymer Housing
  • Meets IEC 60099-4 and IEEE C 62.11 Standards
  • Available With Mounting Hardware
  • Most Typical Voltages Are Available

Specification

DESCRIPTION specification conditions VALUE
Maximum Continuous Operating Voltage VRMSAC 19200 VAC
Maximum Discharge Current IMAXFor 8 x 20 μs Pulse 5000 A
Rated Voltage (L-N) VR (L24 kV
Maximum DC Reference Voltage VDCREFAt 1 mA 34.4 kV
Maximum Residual Voltage VRESAt Steep of 1 x 10 µs Pulse 81.6 kV
Maximum Residual Voltage VRESFor Lightning Impulse 8 x 20 µs 70.4 kV
Maximum Residual Voltage VRESFor Switching Impulse 30 x 60 µs 60 kV
Withstand Capability ISWCFor Current Impulse 4 x 10 µs 65 kA
Housing Insulation Level VBILFor Lighning Impulse 92 kV
Housing Insulation Level VBILAt Power Frequency, Wet 1 Minute64 kV
Mechanical Strength Torsional Str. Tor50 N m
Mechanical Strength Cantilever Str. Can.147 N m
Creepage Distance Creepage674 mm
Dimension - A A1.18 in
Dimension - B B1.18 in
Dimension - C C11.259 in
Dimension - D D13.625 in
Dimension - E E2.047 in
Dimension - FF4.331 in