CK5W-6/17
Notes
- Typical response time is 25 nS maximum L-N and 100nS maximum N-PE.
- Meets IEC600 99-4.
Specification
DESCRIPTION | specification | conditions | VALUE |
---|---|---|---|
Maximum Continuous Operating Voltage | VRMS | AC | 4800 VAC |
Maximum Discharge Current | IMAX | For 8 x 20 μs Pulse | 5000 A |
Rated Voltage (L-N) | VR (L | 6 kV | |
Maximum DC Reference Voltage | VDCREF | At 1 mA | 8.6 kV |
Maximum Residual Voltage | VRES | At Steep of 1 x 10 µs Pulse | 20.4 kV |
Maximum Residual Voltage | VRES | For Lightning Impulse 8 x 20 µs | 17.6 kV |
Maximum Residual Voltage | VRES | For Switching Impulse 30 x 60 µs | 15 kV |
Withstand Capability | ISWC | For Current Impulse 4 x 10 µs | 65 kA |
Housing Insulation Level | VBIL | For Lighning Impulse | 23 kV |
Housing Insulation Level | VBIL | At Power Frequency, Wet 1 Minute | 16 kV |
Mechanical Strength Torsional | Str. Tor | 50 N m | |
Mechanical Strength Cantilever | Str. Can. | 147 N m | |
Creepage Distance | Creepage | 385 mm | |
Dimension - A | A | 1.18 in | |
Dimension - B | B | 1.18 in | |
Dimension - C | C | 7.007 in | |
Dimension - D | D | 9.375 in | |
Dimension - E | E | 2.047 in | |
Dimension - F | F | 4.331 in |