CK5W-9/29


Notes

  • Typical response time is 25 nS maximum L-N and 100nS maximum N-PE.
  • Meets IEC600 99-4.

Request a Quote

Specification

DESCRIPTION specification conditions VALUE
Maximum Continuous Operating VoltageVRMSAC7200 VAC
Maximum Discharge CurrentIMAXFor 8 x 20 μs Pulse5000 A
Rated Voltage (L-N)VR (L9 kV
Maximum DC Reference VoltageVDCREFAt 1 mA12.9 kV
Maximum Residual VoltageVRESAt Steep of 1 x 10 µs Pulse30.6 kV
Maximum Residual VoltageVRESFor Lightning Impulse 8 x 20 µs26.4 kV
Maximum Residual VoltageVRESFor Switching Impulse 30 x 60 µs22.5 kV
Withstand CapabilityISWCFor Current Impulse 4 x 10 µs65 kA
Housing Insulation LevelVBILFor Lighning Impulse34.5 kV
Housing Insulation LevelVBILAt Power Frequency, Wet 1 Minute24 kV
Mechanical Strength TorsionalStr. Tor50 N m
Mechanical Strength CantileverStr. Can.147 N m
Creepage DistanceCreepage385 mm
Dimension - AA1.18 in
Dimension - BB1.18 in
Dimension - CC7.007 in
Dimension - DD9.375 in
Dimension - EE2.047 in
Dimension - FF4.331 in