HE3240P42MT1CTA


Notes

  • ANIS / UL 1449 4th Edition Type 1 / Type 2.
  • Connection wires 12 AWG, 300 mm.

Specification

DESCRIPTION specification conditions VALUE
Operating Temperature RangeOP TEMP-40 to 75 °C
System VoltageVSYS50 or 60 Hz240 / 480 V
TopologySplit Phase
Nominal Discharge CurrentIn20000 A
Voltage Protection Range (Line to Neutral)VPR (L At 6 kV per 3 kA1200 V
Voltage Protection Range (Line to Ground)VPR (L At 6 kV per 3 kA1200 V
Voltage Protection Range (Neutral to Ground)VPR (N At 6 kV per 3 kA1200 V
Voltage Protection Range (Line to Line)VPR (L At 6 kV per 3 kA2000 V
Surge Capacity per PhaseI(TM) Phase200000 A
Surge Capacity per ModeI(TM) Mode100000 A
Maximum Continuous Operating VoltageMCOVAll available modes unless otherwise specified.320 V
Maximum Continuous Operating VoltageMCOV (L Line to Line550 V
Operating Humidity RangeHumidityRelative at 25 °C5 - 95 %
Maximum Operating AltitudeAltitude3000 M