- ANIS / UL 1449 4th Edition Type 1 / Type 2.
- Connection wires 12 AWG, 300 mm.
Specification
DESCRIPTION | specification | conditions | VALUE |
---|---|---|---|
Operating Temperature Range | OP TEMP | -40 to 75 °C | |
System Voltage | VSYS | 50 or 60 Hz | 240 / 480 V |
Topology | Split Phase | ||
Nominal Discharge Current | In | 20000 A | |
Voltage Protection Range (Line to Neutral) | VPR (L | At 6 kV per 3 kA | 1200 V |
Voltage Protection Range (Line to Ground) | VPR (L | At 6 kV per 3 kA | 1200 V |
Voltage Protection Range (Neutral to Ground) | VPR (N | At 6 kV per 3 kA | 1200 V |
Voltage Protection Range (Line to Line) | VPR (L | At 6 kV per 3 kA | 2000 V |
Surge Capacity per Phase | I(TM) Phase | 250000 A | |
Surge Capacity per Mode | I(TM) Mode | 125000 A | |
Maximum Continuous Operating Voltage | MCOV | All available modes unless otherwise specified. | 320 V |
Maximum Continuous Operating Voltage | MCOV (L | Line to Line | 550 V |
Operating Humidity Range | Humidity | Relative at 25 °C | 5 - 95 % |