- Device data taken at 25°C.
- Typical response time is less than 15 nanoseconds.
Specification
DESCRIPTION | specification | conditions | VALUE |
---|---|---|---|
Operational Temperature Range | OP TEMP | -55 to 125 °C | |
Typical Capacitance | C | At 1 kHz | 12000 pF |
Maximum Continuous Operating Voltage AC | VRRMS | 300 V | |
Maximum Continuous Operating Voltage DC | VDC | 385 V | |
Minimum Varistor Voltage | VN(DC) MIN | At 1 mA | 423 V |
Nominal Varistor Voltage | VN(DC) NOM | At 1 mA | 470 V |
Maximum Varistor Voltage | VN(DC) MAX | At 1 mA | 517 V |
Maximum Energy | WMAX | At 2 ms | 1500 J |
Maximum Clamping Voltage | VC | At IC | 775 V |
Clamping Current | IC | 800 A | |
Maximum Peak Surge Current | IP | 100000 A | |
Maximum Peak Surge Current | IP | For 8 x 20 μs Pulse | 80000 A |
Maximum Power Dissipation | PD MAX | 2.75 W |