CK5W-27/76.5


Notes

  • Typical response time is 25 nS maximum L-N and 100nS maximum N-PE.
  • Meets IEC600 99-4.

Request a Quote

Specification

DESCRIPTION specification conditions VALUE
Maximum Continuous Operating VoltageVRMSAC21600 VAC
Maximum Discharge CurrentIMAXFor 8 x 20 μs Pulse5000 A
Rated Voltage (L-N)VR (L27 kV
Maximum DC Reference VoltageVDCREFAt 1 mA38.7 kV
Maximum Residual VoltageVRESAt Steep of 1 x 10 µs Pulse91.8 kV
Maximum Residual VoltageVRESFor Lightning Impulse 8 x 20 µs79.2 kV
Maximum Residual VoltageVRESFor Switching Impulse 30 x 60 µs67.5 kV
Withstand CapabilityISWCFor Current Impulse 4 x 10 µs65 kA
Housing Insulation LevelVBILFor Lighning Impulse103.5 kV
Housing Insulation LevelVBILAt Power Frequency, Wet 1 Minute72 kV
Mechanical Strength TorsionalStr. Tor50 N m
Mechanical Strength CantileverStr. Can.147 N m
Creepage DistanceCreepage818 mm
Dimension - AA1.18 in
Dimension - BB1.18 in
Dimension - CC13.385 in
Dimension - DD15.75 in
Dimension - EE2.047 in
Dimension - FF4.331 in