DRS180/3PN
Notes
- Typical response time is 25 nS maximum L-N and 100nS maximum N-PE.
Specification
DESCRIPTION | specification | conditions | VALUE |
---|---|---|---|
Maximum Continuous Operating Voltage | VDC | DC | 230 VDC |
Operating Temperature Minimum | TOPG | -40 C | |
Operating Temperature Minimum | TOPG | 80 C | |
Frequency Maximum | fmin | 48 Hz | |
Frequency Maximum | fmas | 62 Hz | |
Degree of Protection | Protection | IP20 | |
Number of Poles | Poles | 4 | |
Maximum Continuous Operating Voltage | MCOV (VAC) | 180 VAC | |
Maximum Discharge Current [UL] | IMAX | For 8 x 20 μs Pulse | 50000 A |
Nominal Discharge Current | In | For 8 x 20 μs Pulse | 20000 A |
Short-Circuit Current Rating [UL] | ISCCR | 200000 A | |
Residual Current [UL] | Ipe (IRE) [UL] | At VC | 100 µA |
Follow Current Interruption Rating | Ifi | At MCOV | 100 A |
Response time | tA | 100 nS | |
Protection Level (L-N) | VP (L | V | 1000 |
Protection Level (L-N) | VP (L | At VPR | 700 V |
Protection Level (N-PE) | VP (N | For 1.2 x 50 µs Pulse | 1500 V |
Rated Voltage (L-N) | VR (L | 120 kV | |
Rated Voltage (L-L) | VR (L | 208 kV |