DRS180/PN

Specification Conditions Value
VDC DC 230 VDC
TOPG -40 C
TOPG 80 C
fmin 48 Hz
fmax 62 Hz
Protection IP20
Poles 2
MCOV(VAC) 180 VAC
IMAX [UL] For 8 x 20 μs Pulse 50000 A
IN For 8 x 20 μs Pulse 20000 A
ISCCR [UL] 200000 A
Ipe (IRE) [UL] At VC 100 µA
Ifi At MCOV 100 A
tA 100 nS
VP (L-N) 1000 V
VP (L-N) At VPR 700 V
VP (N-PE) For 1.2 x 50 µs Pulse 1500 V
VR (L-N) 120 kV
  • Typical response time is 25 nS maximum L-N and 100nS maximum N-PE.
rUL RoHS