DESCRIPTION specification conditions VALUE
Maximum Continuous Operating Voltage VDCDC 560 VDC
Operating Temperature Minimum TOPG-40 C
Operating Temperature Minimum TOPG80 C
Frequency Maximum fmin48 Hz
Frequency Maximum fmas62 Hz
Degree of Protection ProtectionIP20
Number of Poles Poles4
Maximum Continuous Operating Voltage MCOV (VAC)420 VAC
Maximum Discharge Current [UL] IMAXFor 8 x 20 μs Pulse 50000 A
Nominal Discharge Current InFor 8 x 20 μs Pulse 20000 A
Short-Circuit Current Rating [UL] ISCCR200000 A
Residual Current [UL] Ipe (IRE) [UL]At VC 100 µA
Response time tA25 nS
Protection Level (L-N) VP (LV 2000
Protection Level (L-N) VP (LAt VPR1500 V
Rated Voltage (L-N) VR (L347 kV
Rated Voltage (L-L)VR (L600 kV